contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Overview

HP Parallel 3 Phase Uninterruptible Power Systems (UPS RP36000/3)

 

Power protection in the data center is critical to maintain up time, and the increased densities in data centers is driving the need for uninterruptible power with increased power density, power efficiency, and flexibility. The HP RP36000/3 does just that. This pre-racked uninterruptible power systems provides 36 kilowatts (KW) of power or 24KW with N+1 redundancy. Housed in a single rack cabinet, (HP Rack 10000 Series G2 42U) it can be expanded to 60KW with N+1 simply by installing up to 3 additional RP12000/3 UPS Modules. Digital signal processing, UPS paralleling, and a new On-line On Demand hybrid technology answer the demands for density, redundancy, efficiency and flexibility.

On-line On Demand combines the high efficiency of a line interactive UPS, up to 97%, with the stability of a double conversion on-line UPS when power fluctuates beyond acceptable limits. Hot swappable batteries and electronics modules and an automatic bypass reduce MTTER (mean time to repair) - down time in the event service is needed.

 
RP36000/3 Front
RP36000/3 Rear
1. Power bus bar
1.Power bus bar
2.Cabling wire tray (6U)
2.Input and output connections for RP12000/3 UPS Modules
3.RP12000/3 UPS Modules (qty3)
3.Cabling wire tray (6U)
4.HP 10000 Series G2 42U rack with front and rear doors4.RP12000/3 UPS Expansion Modules (qty3)

Models
HP RP36000/3HP RP36000/3 Uninterruptible Power System NA
AF438A
 HP RP36000/3 Uninterruptible Power System INTL
AF439A

Related Options
Expansion Upgrade for HP RPS36000/3HP RP12000/3 UPS Expansion Module 6U NA
AF436A
HP RP12000/3 UPS Expansion Module 6U INTL
AF437A

Key Features
  • State-of-the-art UPS paralleling technology provides no single point of failure
  • Modular design for growth and flexibility
  • Configured to Order in 36kW, 48kW, and 60kW configurations
  • Unity Rated, volt amperage out equals wattage out for minimum lose
  • On-line On Demand hybrid technology provide industry leading efficiency
  • Hot-swappable battery and electronics modules provide ease of maintenance and faster time to repair
  • Enhanced Battery Management (EBM) extends battery life and improved battery monitoring
  • Optional Extended Runtime Modules (ERMs) can extend up time during a power failure
  • Enhanced front panel display for easy configuration
  • The HP UPS Management Module is included for remote management and monitoring from most web browsers
  • Backed by a limited three-year warranty, HP's pre-failure warning for batteries
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Product Highlights

NOTE: For a brief, printer friendly data sheet that describes this product and informs you of the essential capabilities and specifications, please visit: http://h71028.www7.hp.com/ERC/downloads/4AA1-5885ENW.pdf.
Superior power conditioning and thermal efficiency with On-line On Demand technology and Unity RatingWhen apparent power (VA) equals true power (Watts), the UPS is said to be unity rated (or power factor correction=unity=maximum efficiency). Also, the HP RP36000/3 UPS uses On-line On Demand hybrid technology which operates in line interactive mode during general use to maximize efficiency and minimize heat output. If input voltage fluctuates outside of the established range, such as if a generator comes on line, the UPS immediately switches to double conversion on-line mode to provide the cleanest power possible. This hybrid technology provides 97% efficiency in standard mode, even with output loads as low as 40% of maximum.

Superior Battery ManagementEach HP RP12000/3 UPS Module incorporates Enhanced Battery Management: an exclusive, patented technology that doubles battery service life, optimizes battery recharge time, and provides advance notice of pending battery failure. With Enhanced Battery Management, you have a lower total cost of ownership and receive the best in the industry protection for your critical equipment.

State-of-the-art UPS Paralleling Technology

Configured to order, the HP RP36000/3 UPS ships with three HP RP12000/3 UPS Modules, the power bus bar, and the wiring cabinet installed in an HP Rack 10000 G2 Series 42U rack cabinet. Each module houses its own electronics, batteries, and intelligent automatic bypass module for maximum redundancy. A unique patented state-of-the-art UPS paralleling technology allows all the modules to function independently of each other while presenting themselves as a single, much larger UPS. Should one of the modules fail then the remaining modules seamlessly redistribute the new load requirement through an automatic load sharing process (with transparent transfer time). And since both the logic and electronics are housed in the each of the individual HP RP12000/3 UPS Modules this technology eliminates system-level single points of failure. The base configuration can be configured as either a 36kW UPS or a 24kW parallel UPS with N+1 redundancy. Up to three additional HP RP12000/3 UPS Modules can be added to provide a maximum of 60 kilowatts with N+1 redundancy (in a single 42U rack).

With its high speed Digital Signal Processing (DSP) design all necessary information for paralleling is available to all UPS modules and eliminates single points of failure. The load share control algorithms maintain synchronization and load balance by constantly making minute adjustments to variations in the output power requirements. The paralleling technology in the HP RP36000/3 UPS provides the highest level of reliability and system availability.


Ease of serviceability through hot-swappable batteries and electronics modules

The HP RP36000/3 UPS and HP RP12000/3 UPS Modules have a uniquely designed architecture, consisting of separate, hot swappable battery and electronics modules. Further, a built-in intelligent automatic bypass feature ensures continuous power to your connected load even while the modules are being replaced. Ease of maintenance and serviceability

  • Faster time to repair (low MTTR)
  • Automatic and manual bypass
  • Increased flexibility through modular design

Increase battery back-up time with up to four Extended Runtime ModulesEach HP RP12000/3 UPS Module supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time, should you have a sudden brief power outage. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. For maximum runtime the ERMs should be configured evenly across all UPS Expansion Modules in the HP RP36000/3 UPS. For more information on battery back up times, please refer to the Back-up Times Chart or the Runtime Calculator located at www.hp.com/products/ups

Remote management increase flexibility The HP RP36000/3 systems can be fully configured and monitored from the any of the front management LCDs. For remote management the HP UPS Management Module is included at no charge and provides an embedded web interface allowing the UPS to be managed from anywhere on the network.
NOTE: for more information on the UPS Management Module please see:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/software/module/ups/index.html

Remote Emergency Power Off Feature

The HP RP36000/3 UPS includes an isolated REPO (Remote Emergency Power Off) port. The REPO feature allows the power to the UPS outlets to be switched off from a remote location. For more information, refer the HP RP36000/3 UPS user manual.


Flexible output configuration

Output may be hardwired to a remote power panel, such as the HP Power Distribution Rack, to a wall mounted distribution panel, or optionally via the UPS Output Modules which provide two 3 phase connections per HP RP12000/3 UPS Modules to connect directly to adjacent racks of equipment.


Output Configuration Options
HP Power Distribution Rack

The HP Power Distribution Rack enhances power management in the data center by moving power distribution to the row level. Decentralizing power improves cable management, decreases diagnostic time for problems, and saves installation costs by reducing the size and number of long power feeds required to reach from large wall mounted distribution units. Housed in a single HP Rack 10000 G2 42U rack cabinet, the HP PDR also save floor space and allows you to move heat robbing transformers off of the data center floor improving cooling.

Fully redundant inputs and outputs, can power large numbers of racks with shorter cable runs than conventional site level power distribution systems while providing dependable power to protect valuable IT hardware. Individual branch circuit monitoring and redundant management modules insure you can always determine status and power consumption of each attached rack.

NOTE: for more information on the HP Power Distribution Rack please see: www.hp.com/go/pdr


Wall mounted distribution panelThe HP RP36000/3 UPS output may be connected to a customer supplied wall mounted distribution panel with a variety of breakers. Panel capacity (amperage) should be determined by the final output power the UPS is configured for. The maximum panel size necessary would be 225A (NA) or 125A (INTL)

Output Modules and Jumpers

Output modules attach directly to each HP RP12000/3 UPS Modules in the configuration. Each output module provides two L15-30R out puts (NA) or 2 IEC 309 516C9 (16A, 3 phase) outlets (INTL). By using 3 phase jumper cables the output modules can be connected directly to HP 3 Phase Modular or Monitored PDUs in several individual racks. Because of the UPS Parallel design even a loss of a HP RP12000/3 UPS Expansion Module would not interrupt the load on the output module attached to it. Up to 6 Output Modules can be configured in a fully loaded HP Parallel UPS.


HP UPS Management Module

The HP UPS Management Module (included) enables you to monitor and manage power environments through comprehensive control of HP UPSs. The HP UPS Management Module can support either a single UPS configuration or provides additional power protection with support for dual redundant UPS configuration for no-single-point-of-failure. The additional serial ports will provide greater power management control and flexible monitoring.
The management module can be configured to send alert traps to HP Systems Insight Manager and other SNMP management programs or used as a standalone management system. This flexibility enables you to monitor and manage UPSs through the network. To facilitate day-to-day maintenance tasks, the embedded management software provides detailed system logs.
The HP UPS Management Module provides remote management of a UPS by connecting the UPS directly to the network. Configuration & Management of the UPS from anywhere and at anytime via a standard web browser.

NOTE: For more information on the UPS Management Module please see: http://h18004.www1.hp.com/products/servers/proliantstorage/powerprotection/
software/module/ups/index.html


Configure to Order

Each HP Parallel UPS is configured to order in either a 36kW, 48kW or 60kW configuration. The base RP36000/3 configuration includes an HP 10000G2 series 42U rack with front and rear doors, a wiring tray installed in the bottom 6U of the rack, the power bus bar installed in the rear of the rack, and three RP12000/3 UPS Expansion Modules with communication cards and one UPS Management Module preinstalled. Up to three additional RP12000/3 UPS Expansion Modules can be installed in the same rack and shipped directly to the installation site.

Due to weight limitations Extended Runtime Modules will not be shipped in the same rack as the UPS.

Please allow appropriate time for configuration and shipping.

contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Service and Support, HP Care Pack, and Warranty Information

Warranty
  • HP RP12000/3 UPS Expansion Modules are backed by a standard three-year limited warranty; 3-year parts, 1-year Labor, 1-year onsite. Optional UPS HP Care Pack services are also available for purchase. The power bus bar is covered by a 3-year parts only warranty.
  • Pre-Failure Battery Warning and its associated Warranty.
    • The Pre-Failure Battery Warning is proactively detected and notified by a LED indicator light, showing that the battery needs to be replaced. This notice is given 30 days prior to the battery failure. This indicator provides ample time to order a spare battery (1-800-HP-Invent). Avoid storing battery spares as a back up because of short shelf life of the battery. The battery warranty coverage is 3 years for parts. The warranty for the first year of ownership includes parts and labor.
    • Warranty, standard on all HP Uninterruptible Power System (UPS) units, extends the advantage of a HP three-year limited warranty by applying it to the battery before it actually fails. Specifically, the Pre-Failure Battery Warning ensures that when customers receive the notification from their HP UPS that the battery may fail, the battery is replaced free of charge under the warranty. HP maintains the highest standards in the industry, as evidenced by the HP Pre-Failure Battery Warranty.
  • In addition, HP UPSs are covered by a $250,000 equipment protection guarantee. Should your connected equipment get damaged due to a UPS failure, then your damaged equipment is covered to up to $250,000.

NOTE: The $250,000 Equipment Protection Guarantee is offered only in North America.


HP Care Pack Services

These HP Care Pack Services help increase uptime and productivity with rapid-response support on a 24x7 or 13x5 basis. Coverage of UPS batteries is not included with Care Pack Services.

NOTE: For more information on HP Care Pack services, contact any of our worldwide sales offices or resellers or visit our worldwide Web site on the internet at: http://www.hp.com/hps/carepack
NOTE: For more complete information on HP Services offerings, customers and resellers, please visit us at: http://www.hp.com/hps
NOTE: Additional information regarding worldwide limited warranty and technical support is available at: http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html
NOTE: The information contained herein is subject to change without notice and is provided "as is" without warranty of any kind.
NOTE: The warranties for HP products and services are set forth in the express limited warranty statements accompanying such products and services.

contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Related Options

Care Pack Services
4-Hour On-site Service, 5-Day x 13-Hour Coverage, 3 Years, Electronic
UH804E
4-Hour On-site Service, 7-Day x 24-Hour Coverage, 3 Years, Electronic
UH805E
6-Hour Call to Repair, On-site Service, 7-Day x 24-Hour Coverage, 3 Years, Electronic
UH806E
NOTE: Additional Care Packs are available.
NOTE: The UPS batteries, power bus bar, and wire tray components are covered by a 3 year parts warranty only.
 

Power Distribution Rack
400 Amp Dual Input Power Distribution Rack, NA
AF514A
200 Amp Dual Input Power Distribution Rack, INTL
AF515A
NOTE: For more information on the HP Power Distribution Rack please go to: www.hp.com/go/pdr.

Extended Runtime Module (WW)
Extended Runtime Module (WW)
NOTE: Each HP R12000/3 UPS Expansion Module supports a maximum of four Extended Runtime Modules (ERM), to further increase your battery back-up time. Each ERM is 3U high and can be automatically detected and configure when attached to the UPS. For maximum runtime, ERMs should be evenly distributed across all UPS Expansion Modules. All installed RP12000/3 UPS Expansion modules should have the same number of ERMs attached. For more information on battery back up times, please refer to the Back-up Times Chart.
AF434A

UPS Output Modules
UPS Output Module, Dual L15-30 (NA)
AF440A
UPS Output Module, Dual IEC 516C9 (INTL)
AF441A

3 Phase Jumper Cables
L15-30P to L15-30R, 5ft (NA)
460151-005
L15-30P to L15-30R, 10ft (NA)
460151-010
L15-30P to L15-30R, 15ft (NA)
460151-015
IEC 516P9 to IEC 516C9, 5ft (INTL)
460153-005
IEC 516P9 to IEC 516C9, 10ft (INTL)
460153-010
IEC 516P9 to IEC 516C9, 15ft (INTL)
460153-015

Rackmount Power Distribution Units (PDUs) and PDU options
North America/Japan
8.6 kVA Modular PDU, 24A 3Ø
AF512A
HP 8.3 kVA S1324 Monitored PDU- single input, 3Ø, 24A (NA/JPN)
AF504A
HP 17.3 kVA S2324 Monitored PDU- dual input, 3Ø24A (NA/JPN)
AF503A
International
HP 3 Phase Modular PDU, 11 kVA, 16A 3Ø
AF513A
HP 11 kVA S1316 Monitored PDU- single input, 3Ø, 16A (INTL)
AF508A
HP 22.1 kVA S2316 Monitored PDU- dual input, 3Ø, 16A (INTL)
AF507A

HP PDU Extension Bars HP C-13 PDU Extension Bar Kit, pair
NOTE: Each extension bar has a C-20 input cord and 7 x C-13 receptacles.
AF500A
Fixed Cord Extension Bars, 100 - 240 VAC
NOTE: Each extension bar has a C-20 input cord and 7 attached 13 inch C-13 power cords for use with 1U servers.
351655-B21
NOTE: Extension bars may be used with any HP PDU that has C-19 outlets

HP PDU Management ModuleHP PDU Management Module
NOTE: For additional information on the PDU Management Module please go to:
http://h18004.www1.hp.com/products/servers/proliantstorage/power-protection/
power-distribution/module/index.html
AF400A

HP Power Cords10A, IEC320 C-14 to IEC320 C-13 Cables, 4.5ft (1.37m), 15 pack
142257-007
10A, IEC320 C-14 to IEC320 C-13 Cables, 4.5ft (1.37m), single 15 pack
142257-006
10A, IEC320 C-14 to IEC320 C-13 Cables, 1.6ft (0.5m), single pack
142257-B28
16A, IEC320 C-19 to IEC320 C-20 Cables, 8ft (2.5m), single pack
295633-B22
16A, IEC320 C-19 to IEC320 C-20 Cables, 6.5ft (2m), single pack
AF574A
16A, IEC320 C-19 to IEC320 C-20 Cables, 4ft (1.2m), single pack
AF575A
16A, IEC320 C-19 to IEC320 C-20 Cables, 3ft (1m), single pack
E7798A
NOTE: For more information on HP power cords please go to: ftp://ftp.compaq.com/pub/products/servers/ProLiantstorage/power-protection/power-cord-option-kits.pdf

Sidewall Panel Kits10642 G2 (42U) Side Panels (set of two) (Graphite Metallic)
AF054A
NOTE: The lightweight, locking side panels for the G2 Series racks come in 3 sections for better handling. Side panels are included with the 22U and 14U racks. 
Rack Stabilization KitsHP 10K G2 600mm Stabilizer Option Kit (Graphite)
AF062A
NOTE: The anti-tip stabilizer kits provide stability and support when equipment is installed, removed or accessed within the rack.
HP Rack Cable Trays Rack Top Cable Tray, 600W (set of 8)
383982-B21

Rack to Rack Adjustable Cable Tray, Aisle Transfer Bridge
NOTE: The Aisle Transfer bridge allows for cabling trays to be connected even across different aisles in the datacenter.

383984-B21
NOTE: These kits mount on the top of the 9000 and 10000 Series rack (except the S10614 rack). Kit color is graphite.
Rack Coupling KitRack Coupling Kit (Carbon)
248929-B21
NOTE: Supported by both the Rack 10000 and Rack 10000 G2 series. Supports 24 in and 600 mm floor tile spacing. The kit is used to join two or more 10000 series racks of the same height together in minutes to create a multi-bay configuration.
NOTE: for a complete list of all HP 10000 G2 Series rack option please go to www.hp.com/go/rackandpower 

Service and Support Offerings
(HP Care Pack Services)
Hardware Installation (Electronic)
NOTE: Covers field installation of an additional RP12000/3 UPS module into an existing RP36000/3. The RP36000/3 must be installed by a qualified electrical contractor. One U4696E Service must be purchased for each additional RP12000/3 UPS Expansion module to be installed.
U4696E
contents
 Overview      Product Highlights      Service and Support, HP Care Pack, and Warranty Information      Related Options      Technical Specifications line.gif (50 bytes)

Technical Specifications

  RP36000/3 Base UPS (NA)RP12000/3 UPS Expansion Module (NA)RP36000/3 Base UPS (INTL)RP12000/3 UPS Expansion Module (INTL)
General Characteristics Power rating (non-redundant)36kW/36kVA12kW/12kVA36kW/36kVA12kW/12kVA
Power rating (N+1)24kW/24kVAEach unit adds 12kW/12kVA for a maximum of 60kW/60kVA24kW/24kVAEach unit adds 12kW/12kVA for a maximum of 60kW/60kVA
Efficiency
>97% at 40% load and above
>97% at 40% load and above
Heat dissipation1113W/3800 BTU371W/1266BTU1113W/3800 BTU371W/1266BTU
Altitude before de-rating1000 meters (3300 ft. ASL)1000 meters (3300 ft. ASL)1000 meters (3300 ft. ASL)1000 meters (3300 ft. ASL)
 
Output CharacteristicsOutput connections
Hardwired to power bus bar or uses optional output modulesConnects to power bus bar or uses optional output modulesHardwired to power bus bar or uses optional output modulesConnects to power bus bar or uses optional output modules
Rated Output voltage
100-120VAC Phase to Neutral
180-255VAC Phase to Phase
208VAC 3Φ Delta or Wye
180-240VAC Phase to Neutral
400v 3Φ Wye
Output configuration
50 or 60Hz auto detecting at startup
50 or 60Hz auto detecting at startup
Frequency regulation
0.1Hz free running
0.1Hz free running
Load power factor range
Lagging: 0.7
Leading: 0.9
Lagging: 0.7
Leading: 0.9
Total output voltage distortion
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies
<3% with IT loads (PFC power supplies)
<5% non-linear or non-PFC power supplies
    
Input CharacteristicsNominal input voltage
208V/120V 3 Phase Wye
5 wire 4 pole
400V/230V 3 Phase Wye
5 wire 4 pole
Voltage range
180 - 255VAC
380- 415VAC
Input Current (100% Load)
3 UPS Modules 150 Amps
3 UPS Modules 80 Amps
4 UPS Modules 200 Amps
4 UPS Modules 100 Amps
5 UPS Modules 225 Amps
5 UPS Modules 125 Amps
6 UPS Modules 225Amps
6 UPS Modules 160Amps

Input Current (N+1)

3 UPS Modules 150 Amps
3 UPS Modules 63 Amps
4 UPS Modules 200 Amps
4 UPS Modules 80 Amps
5 UPS Modules 225 Amps
5 UPS Modules 125 Amps
6 UPS Modules 225 Amps
6 UPS Modules 160 Amps
* Motor rated input breakers are recommended to minimize accidental tripping upon start-up.
** Rate input breakers for 100% future load if at all possible.

 
Battery Characteristics Battery type
Valve regulated lead acid, sealed, maintenance free
Valve regulated lead acid, sealed, maintenance free
Battery runtime (no ERM)
>5 minutes at 100% load
>5 minutes at 100% load
Battery string voltage
240VDC
240VDC
Battery test
Automatic standard, manual available
Automatic standard, manual available
Battery recharge profile
Enhanced Battery Management 3 stage charging technology
Enhanced Battery Management 3 stage charging technology
Battery pre-failure notification
Yes, up to 30 days advance notification
Yes, up to 30 days advance notification
ERM compatibility
Up to 4 per RP12000/3 UPS Expansion Module.
Up to 4 per RP12000/3 UPS Expansion Module.
 
Physical Characteristics Dimensions (HxWxD)78.7 x 39.7 x 24 in (2000 x 1015 x 597 mm)10.3 (6U) x 17.4 x 26 in (267 x 442 x 660 mm)78.7 x 39.7 x 24 in (2000 x 1015 x 597 mm)10.3 (6U) x 17.4 x 26 in (267 x 442 x 660 mm)
Total Chassis Weight without batteries or electronics
653 lb. (396 kg.)100 lb. (46 kg)653 lb. (396 kg.)100 lb. (46 kg)
Total Chassis Weight with batteries and electronics1274 lb. (578 kg)307 lb. (140 kg)1274 lb. (578 kg)307 lb. (140 kg)
ERM Weight
170 lb. (77 kg)
170 lb. (77 kg)
 
Communications and ManagementSoftware compatibility
Ships with HP UPS Management Module
Ships with HP UPS Management Module
Control Panel
Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs
1 per UPS Module
Two lines by 20 characters
Four menu-driven interface buttons
Four status at a glance LEDs
1 per UPS Module
Language support
English, Spanish, French, German
English, Spanish, French, German
REPO Port
Yes, normally open or normally closed available
Yes, normally open or normally closed available
 
CertificationsSafety
UL1778, CUL
CE
EMI
FCC Part 15, Class A
EN62040-2, Class A
Surge Protection
ANSI C62.41, Cat B-3
ANSI C62.41, Cat B-3
Hazardous Materials (RoHS)
EU Directive 2002/95/EC Category 3 (4 of 5)
EU Directive 2002/95/EC Category 3 (4 of 5)

Estimated Backup Times Chart (100% Load) [Minutes]
Estimated Backup Times Chart [Minutes]
Number of modules
Total kW Load
Internal batteries
+ 1 ERM/ Module
+ 2 ERM/ Module
+ 3 ERM/ Module
+ 4 ERM/ Module
5
60
4.7
9.5
17
27
34
4
48
4.7
9.5
17
27
34
3
36
4.7
9.5
17
27
34
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
 
Estimated Backup Times Chart (N+1) [Minutes]
Number of modules
Total kW Load
Internal batteries
+ 1 ERM/ Module
+ 2 ERM/ Module
+ 3 ERM/ Module
+ 4 ERM/ Module
6
60
9
15
22
29
37
5
48
6.9
17
26
34
44
4
36
7.7
18
28
37
47
3
24
9
21
32
43
54
* The above configurations are N+1
NOTE:
Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
NOTE: Additional back times information is available at www.hp.com/products/ups
 

Environment-friendly Products and Approach

End-of-life Management and Recycling

Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2009 Hewlett-Packard Development Company, L.P.
The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.