Overview
|
HP Power Distribution Rack |
|||
|
It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier strain on servers and air conditioning units in the data center. For many companies, this puts data center costs and performance under the spotlight making them essential factors for an efficient IT infrastructure. HP helps companies manage their data centers more effectively to decrease power and cooling costs. The HP Power Distribution Rack (PDR) improves power management in the data center by moving power distribution to the row level. Decentralizing power improves cable management, decreases diagnostic time for problems, and saves installation costs by reducing the size and number of long power feeds required to reach from large wall mounted distribution units. Housed in a single HP Rack 10000 G2 42U rack cabinet, the PDR also saves floor space and allows you to move heat robbing transformers off of the data center floor improving cooling. Capable of delivering 400 amps (NA) / 200 amps (INTL) redundantly, the HP PDR can power several high density racks with shorter cable runs than conventional site level power distribution systems. Fully redundant inputs and outputs provide dependable power while protecting valuable IT hardware with high quality circuit breakers. Individual branch circuit monitoring and redundant management displays provide the local status and power consumption of each attached rack while the remote management module provides secure communication over a browser, through telnet, and even through ModBus protocols. |
|||
![]() |
|||
|
HP Power Distribution Rack
|
|||
| 1. | Maintenance access panel, left and right | 5. | Branch circuit monitoring sensors (not shown) |
| 2. | Management and configuration display, front and rear | 6. | Input circuit breaker, front and rear |
| 3. | Branch circuit breaker panel, front and rear | 7. | Enclosure, HP 10000G2 Series 42U rack with doors |
| 4. | Branch circuit breakers | NEW | PDR Remote Management Module (not shown) |
|
|
|||
|
What's new |
| New pre-installed HP PDR Management Module allows remote management of the PDR via an embedded web engine, telnet, and ModBus. |
|
|
| Models | ||
| HP Power Distribution Rack | 400 Amp Dual Input Power Distribution Rack |
AF514A
|
|
|
Product Features
| Target Applications and Markets | 24/7 data centers | The HP Power Distribution Rack (PDR) enables data centers to provide efficient decentralized power to multiple racks from two separate power sources. Complete redundancy within the HP PDR with its dual inputs supporting dual power panels. High amperage input provides almost twice the capacity of many site level power distribution systems in a smaller foot print. Each HP PDR is capable of providing fully redundant power to multiple racks of various voltage configurations. |
| Small to Medium size data centers | The HP Power Distribution Rack provides flexible and easy to configure power distribution in a small footprint by using a single, standard 10000 G2 42U rack. The transformer-less design helps keep unnecessary heat out of the data center and improves air conditioning. Pre-configured power drops reduce clutter and improve installation and change management while the PDR's local and remote monitoring capabilities insure you can always determine status and power consumption of each attached rack. | |
| Collocation Facilities | The HP Power Distribution Rack allows for easy changes in power configurations across multiple racks. Individual branch circuit monitoring allows power usage to be tracked and recorded on a rack by rack basis. | |
|
|
||
| Customer Challenges/ Requirements |
|
|
|
|
| Model Features Power Distribution Rack | Fully redundant | Dual power paths from input through output including dual management displays |
| Dual high amperage three phase inputs | Fewer large cable runs to the PDR increase efficiency and reduce cable clutter | |
| Dual 42 pole position breaker panels | Each panel is feed by a separate input source and provides for 100-120VAC, 208-240VAC, or 3 phase outputs in any combination | |
| Dual Transient Voltage Surge Suppression (TVSS) | A TVSS module protect s each input from passing transients and surges through to the attached equipment | |
| High quality branch circuit breakers for superior performance | Enterprise grade circuit breakers provide fault protection to individual branch circuits and are available in single pole, dual pole and three pole styles in a variety of amperage ratings | |
| Local and remote power monitoring | Each PDR provides local monitoring through dual displays and includes a PDR Management Module that provides remote monitoring of input power as well as each individual branch circuit output. Remote monitoring can be securely accessed through a standard web browser, telnet, and Modbus RTU or Modbus IP. Warnings and alerts can be sent over SNMP, email, or through either Modbus protocol to provide notice of impending issues before problems arise. | |
| Preconfigured metal clad whips | Precut lengths and preassembled whips save installation time and cost and are certified for a variety of installations | |
|
|
||
| Installation |
|
|
|
Service and Support, HP Care Pack, and Warranty Information
|
The HP PDR is covered by a 3 year parts only warranty. Replacement of
any component requires a qualified electrical contractor. |
|
|
Related Options
| Startup and Commissioning Service | 7x24 after hours Start up and Commissioning
Service Uplift NOTE: 8x5 Standard business hours, Monday through Friday Start up and Commissioning Service is included with the PDR at no additional charge. |
AF516A |
| NOTE: Go to www.hp.com/go/pdr to schedule start up and Commissioning service. | ||
|
|
||
| Circuit Breakers | BREAKER, 20A, SINGLE POLE (110-120 volt) | 455337-001 |
| BREAKER, 30A, SINGLE POLE (110-120 volt) | 455337-002 | |
| BREAKER, 20A, TWO POLE (200-240 volt) | 455337-003 | |
| BREAKER, 30A, TWO POLE (200-240 volt) | 455337-004 | |
| BREAKER, 50A, TWO POLE (200-240 volt) | 455337-005 | |
| BREAKER, 30A, THREE POLE (200-240 volt 3 phase) | 455337-006 | |
| BREAKER, 60A, THREE POLE (200-240 volt 3 phase) | 455337-007 | |
|
|
||
| Pre-Configured Power Cabling | NOTE: Metal clad cables have an addition eight feet of wire beyond the conduit length that is listed. | |
| L5-30 Power Cables | ||
| L5-30R Power cable in flexible metal clad conduit,10 feet | 455237-010 | |
| L5-30R Power cable in flexible metal clad conduit, 20 feet | 455237-020 | |
| L5-30R Power cable in flexible metal clad conduit, 30 feet | 455237-030 | |
| L6-20 Power Cables | ||
| L6-20R Power cable in flexible metal clad conduit, 10 feet | 455238-010 | |
| L6-20R Power cable in flexible metal clad conduit, 20 feet | 455238-020 | |
| L6-20R Power cable in flexible metal clad conduit, 30 feet | 455238-030 | |
| L6-30 Power Cables | ||
| L6-30R Power cable in flexible metal clad conduit, 10 feet | 455239-010 | |
| L6-30R Power cable in flexible metal clad conduit, 20 feet | 455239-020 | |
| L6-30R Power cable in flexible metal clad conduit, 30 feet | 455239-030 | |
| CS8269 Power Cables | ||
| CS8269 Power cable in flexible metal clad conduit,10 feet | 455240-010 | |
| CS8269 Power cable in flexible metal clad conduit, 20 feet | 455240-020 | |
| CS8269 Power cable in flexible metal clad conduit, 30 feet | 455240-030 | |
| NOTE: CS8269 cables are for use with HP Power Distribution Units the have CS8265 inlet cords | ||
| L15-30 Power Cables | ||
| L15-30R Power cable in flexible metal clad conduit, 10 feet | 455241-010 | |
| L15-30R Power cable in flexible metal clad conduit, 20 feet | 455241-020 | |
| L15-30R Power cable in flexible metal clad conduit, 30 feet | 455241-030 | |
| L21-30 Power Cables | ||
| L21-30R Power cable in flexible metal clad conduit, 10 feet | 455242-010 | |
| L21-30R Power cable in flexible metal clad conduit, 20 feet | 455242-020 | |
| L21-30R Power cable in flexible metal clad conduit, 30 feet | 455242-030 | |
| NOTE: Can be used to connect to the HP R8000/3 Uninterruptible Power System (UPS). | ||
| IEC-60309 Power Cables NOTE: IEC309 460C9 uses a 60 amp, 4 wire 3 pole connector for use with the following HP Monitored Power Distribution Unit: HP 17.3 kVA S348 Monitored PDU- single input, 3Ø, 60A. |
||
| IEC-60309 460C9 Power cable in flexible metal clad conduit, 10 feet | 455244-010 | |
| IEC-60309 460C9 Power cable in flexible metal clad conduit, 20 feet | 455244-020 | |
| IEC-60309 460C9 Power cable in flexible metal clad conduit, 30 feet | 455244-030 | |
|
|
||
| Available Rack Options | 600W 10000 G2 Rack Tie Down NOTE: For HP 10000 G2 Series only. The tie down kit is used to secure the rack to the datacenter floor. This is not a Zone 4 approved product. |
AF076A |
| HP 10K G2 600mm Stabilizer Option Kit (Graphite) | AF062A | |
| Rack Coupling Kit (Carbon) NOTE: Supported by both the Rack 10000 and Rack 10000 G2 series. Supports 24 in and 600 mm floor tile spacing. The kit is used to join two or more 10000 series racks of the same height together in minutes to create a multi-bay configuration. |
248929-B21 | |
| 9000/10000 Offset Baying Kit (42U) NOTE: This kit can be used to connect 9000 and 10000 series racks of the same U height together. Kit contents include hardware for connecting racks and a panel to cover the 100mm gap at the rear of the two racks. |
248931-B21 | |
| 10642 G2 (42U) Side Panels (set of two) (Graphite
Metallic) NOTE: The lightweight, locking side panels for the G2 Series racks come in 3 sections for better handling. |
AF054A | |
| Rack Top Cable Trays, 600W NOTE: This is an 8-pack. |
383982-B21 | |
| Rack to Rack Adjustable Cable Tray, Aisle
Transfer Bridge NOTE: The Aisle Transfer bridge allows for cabling trays to be connected even across different aisles in the datacenter. |
383984-B21 | |
| NOTE: These kits mount on the top of the 9000 and 10000 Series rack (except the S10614 rack). Kit color is graphite. |
|
|
Compatibility
| Compatibility Matrix |
| PDU or UPS |
Whip
|
Breaker
|
Poles positions used
|
|
|
2.8 kVA LV mPDU
252663-D71 UPS R3000LV AF422A, AF425A |
L5-30R Power cable
455237-xxx |
30A Single Pole
455337-002 |
One
|
|
| 3.6 kVA HV mPDU 252663-B24 UPS R3000HV AF423A, AF424A |
L6-20R Power Cable
455238-xxx |
20A Two Pole
455337-003 |
Two
|
|
| 4.9 kVA HV mPDU 252663-D72, 252663-D74 UPS R5500 AF426A |
L60-30R Power Cable
455239-xxx |
30A Two Pole
455337-004 |
Two
|
|
| 8.3 kVA HV mPDU (corded) 252663-D73, 252663-D75 |
CS8269 Power Cable
455240-xxx |
50A Two Pole
455337-005 |
Two
|
|
| 8.3 kVA HV mPDU (Hard wired) 252663-B21 |
Not Applicable
|
50A Two Pole
455337-005 |
Two
|
|
| 8.6 kVA 3Ø mPDU AF512A |
L15-30R Power Cable
455241-xxx |
30A Three Pole
455337-006 |
Three
|
|
| UPS R8000/3 AF431A |
L21-30 Power Cord
455242-xxx |
30A Three Pole
455337-006 |
Three
|
|
| S1140 8.3 kVA Monitored PDU AF506A |
CS8269 Power Cable
455240-xxx |
50A Two Pole
455337-005 |
Two
|
|
| S2140 16.6 kVA Monitored PDU AF505A |
CS8269 Power Cable 455240-xxx
(two required) |
50A Two Pole
455337-005 (two required) |
Two per breaker
|
|
| S1324 8.6 kVA Monitored PDU AF504A |
L15-30R Power Cable
455241-xxx |
30A Three Pole
455337-006 |
Three
|
|
| S2324 17.3 kVA Monitored PD AF503A |
L15-30R Power Cable 455241-xxx
(two required) |
30A Three Pole
455337-006 (two required) |
Three per breaker
|
|
| S124 8.3 kVA Monitored PDU AF914A |
L60-30R Power Cable
455239-xxx |
30A Two Pole
455337-004 |
Two
|
|
| S348 17.3 kVA Monitored PDU AF916A |
IEC-60309 460C9 Power Cord 455244-xxx
|
60A Three Pole
455337-007 |
Three
|
|
| NOTE: "-xxx" = power cable length | ||||
| -010 = 10ft (3m) | -015 = 15ft (4.5m) | -020 = 20ft (6m) | ||
|
|
Technical Specifications
| Model |
400 Amp Dual Input PDR
|
|||
| Part number |
AF514A
|
|||
| Rack Information |
10000G2 Series, 42U, Shock Pallet (side panels not included)
|
|||
| Maximum Input (VAC) |
Dual 400A, 208V 60Hz 3Ø Wye
|
|||
| Maximum amperage |
320A per phase
|
|||
| Maximum kVA and KW output per panel |
115kVA/ 115KW
|
|||
| Output voltages |
120V, 208v single phase, 208V 3 phase Delta and 208V
3 phase Wye
|
|||
| Breaker Panels |
2 x 400A, 42 pole
|
|||
| Branch circuit breakers |
Cutler Hammer 1 inch bolt on
|
|||
| Input Breaker |
400 amp 3 pole Cutler Hammer K-Frame
|
|||
| Transient Voltage Surge Suppression | ||||
| UL 1449 SECOND EDITION SURPRESSED VOLTAGE RATING (SVR) |
L-N
|
L-G
|
N-G
|
L-L
|
|
500V
|
500V
|
500V
|
800V
|
|
| EMI/RFI Noise Attenuation |
40 db @ 100kHz
|
|||
| Filter Bandwidth |
10 kHz to 100MHz
|
|||
| Response time |
<0.5 ns
|
|||
| Line Frequency |
47 65 Hz
|
|||
| Line Voltage |
+/- 15% nominal
|
|||
| Operating Temperature |
40° to +140° F (40° to +60°
C)
|
|||
| Relative Humidity |
0 95% non-condensing
|
|||
| Operating Altitude |
0 to 28,000 ft (0 to 91,863.24 m)
|
|||
| Audible Noise |
none
|
|||
| Max Continuous Operating Voltage |
Greater than 115% of nominal voltage
|
|||
| Dimensions | ||||
| Operating | ||||
| (HxDxW) |
78.7 x 39.691 x 24 in (200 x 101.5 x 59.7 cm)
|
|||
| Weight (no breakers) |
510 lbs (231 kg)
|
|||
| Shipping | ||||
| (HxDxW) |
86.22 x 48 x 32 in (219 x 121.92 x 81.28 cm)
|
|||
| Weight |
626 lbs (284 kg)
|
|||
|
|
||
|
Environment-friendly Products and Approach |
End-of-life Management and Recycling | Hewlett-Packard offers end-of-life HP product
return, trade-in, and recycling programs in many geographic areas. For trade-in
information, please go to www.hp.com/go/green.
To recycle your product, please go to: www.hp.com/go/green
or contact your nearest HP sales office. Products returned to HP will be
recycled, recovered or disposed of in a responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment. |
|
|
||
| © Copyright 2008 Hewlett-Packard Development
Company, L.P. The information contained herein is subject to change without notice. The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein. |