Overview

HP Power Distribution Rack

 
It's getting harder to manage a data center efficiently, with rising utility bills and ever-increasing demands due to processor power and server density increases. Growing user requests mean heavier strain on servers and air conditioning units in the data center. For many companies, this puts data center costs and performance under the spotlight-making them essential factors for an efficient IT infrastructure. HP helps companies manage their data centers more effectively to decrease power and cooling costs.

The HP Power Distribution Rack (PDR) improves power management in the data center by moving power distribution to the row level. Decentralizing power improves cable management, decreases diagnostic time for problems, and saves installation costs by reducing the size and number of long power feeds required to reach from large wall mounted distribution units. Housed in a single HP Rack 10000 G2 42U rack cabinet, the PDR also saves floor space and allows you to move heat robbing transformers off of the data center floor improving cooling.

Capable of delivering 400 amps (NA) / 200 amps (INTL) redundantly, the HP PDR can power several high density racks with shorter cable runs than conventional site level power distribution systems. Fully redundant inputs and outputs provide dependable power while protecting valuable IT hardware with high quality circuit breakers. Individual branch circuit monitoring and redundant management modules provide the status and power consumption of each attached rack.

 
 
 
 
HP Power Distribution Rack
 
1. Maintenance access panel, left and right 5. Branch circuit monitoring sensors (not shown)
2. Management and configuration display, front and rear 6. Input circuit breaker, front and rear
3. Branch circuit breaker panel, front and rear 7. Enclosure, HP 10000G2 Series 42U rack with doors
4. Branch circuit breakers    

Models
HP Power Distribution Rack 400 Amp Dual Input Power Distribution Rack
AF514A
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Compatibility      Technical Specifications line.gif (50 bytes)

Product Features

Target Applications and Markets 24/7 data centers The HP Power Distribution Rack (PDR) enables data centers to provide efficient decentralized power to multiple racks from two separate power sources. Complete redundancy within the HP PDR with its dual inputs supporting dual power panels. High amperage input provides almost twice the capacity of many site level power distribution systems in a smaller foot print. Each HP PDR is capable of providing fully redundant power to 13 racks with 8.6KW loads in each or 23 racks with 4.9KW loads.
Small to Medium size data centers The HP Power Distribution Rack provides flexible and easy to configure power distribution in a small footprint by using a single, standard 10000 G2 42U rack. The transformer-less design helps keep unnecessary heat out of the data center and improves air conditioning. Pre-configured power drops reduce clutter and improve installation and change management while the PDR's monitoring capabilities insure you can always determine status and power consumption of each attached rack.
Collocation Facilities The HP Power Distribution Rack allows for easy changes in power configurations across multiple racks. Individual branch circuit monitoring allows power usage to be tracked and recorded on a rack by rack basis.

Customer Challenges/
Requirements
  • Easy access to power multiple servers, storage and other rack mount equipment
  • Reduce cabling to improve airflow
  • Ease installation and upgrades to power distribution
  • Accurately monitor each branch circuit to evaluate power usage

Model Features – Power Distribution Rack Fully redundant Dual power paths from input through output including dual management displays
Dual high amperage three phase inputs Fewer large cable runs to the PDR increase efficiency
Dual 42 pole position breaker panels Each panel is feed by a separate input source and provides for 100-120VAC, 208-240VAC, or 3 phase outputs in any combination
Dual Transient Voltage Surge Suppression (TVSS) A TVSS module protect s each input from passing transients and surges through to the attached equipment
Dual management displays One front and one rear display provide redundancy and ease configuration
High quality branch circuit breakers for superior performance Commercial grade circuit breakers provide fault protection to individual branch circuits and are available in single pole, dual pole and three pole styles in a variety of amperage ratings
Power monitoring Each PDR chassis provides local monitoring of the both input loads as well as individual branch circuits. Alarms provide notice of impending issues before problems arise
Preconfigured metal clad whips Precut lengths and preassembled whips save installation time and cost and are certified for a variety of installations

Installation
  • The HP Power Distribution Rack must be installed by a qualified electrical contractor
  • It is strongly recommended that the HP PDR be bayed to other racks in the row or secured by HP 10000 G2 Stabilizing feet or 600W 10000 G2 Rack Tie Down kit
  • If power cables are run above the racks the HP Rack Top Cable Trays are recommended
  • Start up and Commissioning service is included at no additional charge and must be completed to validate warranty protection. Start up and commissioning service may be performed Monday through Friday during standard business hours. Optional 7x24 Start up and commissioning service is available.
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Compatibility      Technical Specifications line.gif (50 bytes)

Service and Support, HP Care Pack, and Warranty Information

The HP PDR is covered by a 3 year parts only warranty. Replacement of any component requires a qualified electrical contractor.
NOTE: Additional information regarding worldwide limited warranty and technical support is available at:
http://h18004.www1.hp.com/products/servers/platforms/warranty/index.html

NOTE: The information contained herein is subject to change without notice and is provided "as is" without warranty of any kind.
NOTE: The warranties for HP products and services are set forth in the express limited warranty statements accompanying such products and services.
NOTE: Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Compatibility      Technical Specifications line.gif (50 bytes)

Related Options

Startup and Commissioning Service 7x24 after hours Start up and Commissioning Service
NOTE: 8x5 Standard business hours, Monday through Friday included at no additional charge.
AF516A
NOTE: Go to www.hp.com/go/pdr to schedule start up and Commissioning service.  

Circuit Breakers BREAKER, 20A, SINGLE POLE 455337-001
BREAKER, 30A, SINGLE POLE 455337-002
BREAKER, 20A, TWO POLE 455337-003
BREAKER, 30A, TWO POLE 455337-004
BREAKER, 50A, TWO POLE 455337-005
BREAKER, 30A, THREE POLE 455337-006
BREAKER, 60A, THREE POLE 455337-007

Pre-Configured Power Cabling NOTE: Metal clad cables have an addition eight feet of wire beyond the conduit length that is listed.
L5-30 Power Cables
L5-30R Power cable in flexible metal clad conduit, 5 feet 455237-005
L5-30R Power cable in flexible metal clad conduit,10 feet 455237-010
L5-30R Power cable in flexible metal clad conduit,15 feet 455237-015
L5-30R Power cable in flexible metal clad conduit, 20 feet 455237-020
L5-30R Power cable in flexible metal clad conduit, 30 feet 455237-030
L6-20 Power Cables
L6-20R Power cable in flexible metal clad conduit, 5 feet 455238-005
L6-20R Power cable in flexible metal clad conduit, 10 feet 455238-010
L6-20R Power cable in flexible metal clad conduit, 15 feet 455238-015
L6-20R Power cable in flexible metal clad conduit, 20 feet 455238-020
L6-20R Power cable in flexible metal clad conduit, 30 feet 455238-030
L6-30 Power Cables
L6-30R Power cable in flexible metal clad conduit, 5 feet 455239-005
L6-30R Power cable in flexible metal clad conduit, 10 feet 455239-010
L6-30R Power cable in flexible metal clad conduit, 15 feet 455239-015
L6-30R Power cable in flexible metal clad conduit, 20 feet 455239-020
L6-30R Power cable in flexible metal clad conduit, 30 feet 455239-030
CS8269 Power Cables
CS8269 Power cable in flexible metal clad conduit, 5 feet 455240-005
CS8269 Power cable in flexible metal clad conduit,10 feet 455240-010
CS8269 Power cable in flexible metal clad conduit, 15 feet 455240-015
CS8269 Power cable in flexible metal clad conduit, 20 feet 455240-020
CS8269 Power cable in flexible metal clad conduit, 30 feet 455240-030
NOTE: CS8269 cables are for use with HP Power Distribution Units the have CS8265 inlet cords
L15-30 Power Cables
L15-30R Power cable in flexible metal clad conduit, 5 feet 455241-005
L15-30R Power cable in flexible metal clad conduit, 10 feet 455241-010
L15-30R Power cable in flexible metal clad conduit, 15 feet 455241-015
L15-30R Power cable in flexible metal clad conduit, 20 feet 455241-020
L15-30R Power cable in flexible metal clad conduit, 30 feet 455241-030
L21-30 Power Cables
L21-30R Power cable in flexible metal clad conduit, 5 feet 455242-005
L21-30R Power cable in flexible metal clad conduit, 10 feet 455242-010
L21-30R Power cable in flexible metal clad conduit, 15 feet 455242-015
L21-30R Power cable in flexible metal clad conduit, 20 feet 455242-020
L21-30R Power cable in flexible metal clad conduit, 30 feet 455242-030
NOTE: Can be used to connect to the HP R8000/3 Uninterruptible Power System (UPS).
IEC-60309 Power Cables
NOTE: IEC309 460C9 uses a 60 amp, 4 wire 3 pole connector for use with the following HP Monitored Power Distribution Unit: HP 17.3 kVA S348 Monitored PDU- single input, 3Ø, 60A.
IEC-60309 460C9 Power cable in flexible metal clad conduit, 5 feet 455244-005
IEC-60309 460C9 Power cable in flexible metal clad conduit, 10 feet 455244-010
IEC-60309 460C9 Power cable in flexible metal clad conduit, 15 feet 455244-015
IEC-60309 460C9 Power cable in flexible metal clad conduit, 20 feet 455244-020
IEC-60309 460C9 Power cable in flexible metal clad conduit, 30 feet 455244-030

Available Rack Options 600W 10000 G2 Rack Tie Down
NOTE: For HP 10000 G2 Series only. The tie down kit is used to secure the rack to the datacenter floor. This is not a Zone 4 approved product.
AF076A
HP 10K G2 600mm Stabilizer Option Kit (Graphite) AF062A
Rack Coupling Kit (Carbon)
NOTE: Supported by both the Rack 10000 and Rack 10000 G2 series. Supports 24 in and 600 mm floor tile spacing. The kit is used to join two or more 10000 series racks of the same height together in minutes to create a multi-bay configuration.
248929-B21
9000/10000 Offset Baying Kit (42U)
NOTE: This kit can be used to connect 9000 and 10000 series racks of the same U height together. Kit contents include hardware for connecting racks and a panel to cover the 100mm gap at the rear of the two racks.
248931-B21
10642 G2 (42U) Side Panels (set of two) (Graphite Metallic)
NOTE: The lightweight, locking side panels for the G2 Series racks come in 3 sections for better handling.
AF054A
Rack Top Cable Tray, 600W 383982-B21
Rack to Rack Adjustable Cable Tray, Aisle Transfer Bridge
NOTE: The Aisle Transfer bridge allows for cabling trays to be connected even across different aisles in the datacenter.
383984-B21
NOTE: These kits mount on the top of the 9000 and 10000 Series rack (except the S10614 rack). Kit color is graphite.
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Compatibility      Technical Specifications line.gif (50 bytes)

Compatibility

Compatibility Matrix
PDU or UPS
Whip
Breaker
Poles positions used
2.8 kVA LV mPDU
252663-D71
UPS R3000LV AF422A, AF425A
L5-30R Power cable
455237-xxx
30A Single Pole
4555337-002
One
3.6 kVA HV mPDU
252663-B24
UPS R3000HV AF423A, AF424A
L6-20R Power Cable
455283-xxx
20A Two Pole
455337-003
Two
4.9 kVA HV mPDU
252663-D72, 252663-D74
UPS R5500 AF426A
L60-30R Power Cable
455239-xxx
30A Two Pole
455337-004
Two
8.3 kVA HV mPDU (corded) 252663-D73, 252663-D75
CS8269 Power Cable 4
55240-xxx
50A Two Pole
455337-005
Two
8.3 kVA HV mPDU (Hard wired) 252663-B21
Not Applicable
50A Two Pole
455337-005
Two
8.6 kVA 3Ø mPDU
AF512A
L15-30R Power Cable
455241-xxx
30A Three Pole
455337-006
Three
UPS R8000/3 AF431A
L21-30 Power Cord
455242-xxx
30A Three Pole
455337-006
Three
S1140 8.3 kVA Monitored PDU AF506A
CS8269 Power Cable
455240-xxx
50A Two Pole
455337-005
Two
S2140 16.6 kVA Monitored PDU AF505A
CS8269 Power Cable x2 455240-xxx
50A Two Pole x2
455337-005
Two
S1324 8.6 kVA Monitored PDU AF504A
L15-30R Power Cable
455241-xxx
30A Three Pole
455337-006
Three
S2324 17.3 kVA Monitored PD AF503A
L15-30R Power Cable x2 455241-xxx
30A Three Pole x 2
455337-006
Three
S124 8.3 kVA Monitored PDU AF914A
L60-30R Power Cable
455239-xxx
30A Two Pole
455337-004
Two
S348 17.3 kVA Monitored PDU
AF916A
IEC-60309 460C9 Power Cord 455244-xxx
60A Three Pole
455337-007
Three
NOTE: "-xxx" = power cable length
-050 = 5ft (1.5m) -010 = 10ft (3m) -015 = 15ft (4.5m) -015 = 15ft (4.5m) -020 = 20ft (6m)
contents
 Overview      Product Features      Service and Support, HP Care Pack, and Warranty Information      Related Options      Compatibility      Technical Specifications line.gif (50 bytes)

Technical Specifications

Model
400 Amp Dual Input PDR
Part number
AF514A
Rack Information
10000G2 Series, 42U, Shock Pallet
Input (VAC)
Dual 400A, 208V 60Hz 3Ø Wye
Maximum amperage
320A per phase
Maximum kVA and KW output
116kVA/ 116KW
Output voltages
120V, 208v single phase, 208V 3 phase Delta and 208V 3 phase Wye
Breaker Panels
2 x 400A, 42 pole
Branch circuit breakers
Cutler Hammer 1 inch bolt on
Input Breaker
400 amp 3 pole Cutler Hammer K-Frame
   
Transient Voltage Surge Suppression
UL 1449 SECOND EDITION SURPRESSED VOLTAGE RATING (SVR)
L-N
L-G
N-G
L-L
500V
500V
500V
800V
EMI/RFI Noise Attenuation
40 db @ 100kHz
Filter Bandwidth
10 kHz to 100MHz
Response time
<0.5 ns
Line Frequency
47 – 65 Hz
Line Voltage
+/- 15% nominal
Operating Temperature
–40° to +140° F (–40° to +60° C)
Relative Humidity
0 – 95% non-condensing
Operating Altitude
0 to 28,000 ft (0 to 91,863.24 m)
Audible Noise
none
Max Continuous Operating Voltage
Greater than 115% of nominal voltage
Dimensions  
Operating  
   (HxDxW)
78.7 x 39.691 x 24 in (200 x 101.5 x 59.7 cm)
   Weight (no breakers)
510 lbs (231 kg)
Shipping  
   (HxDxW)
86.22 x 48 x 32 in (219 x 121.92 x 81.28 cm)
   Weight
626 lbs (284 kg)

Environment-friendly Products and Approach

End-of-life Management and Recycling Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to www.hp.com/go/green. To recycle your product, please go to: www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2007 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.

   DA-12859 3 - Version 3 - December 7, 2007