HP Dynamic Smart Cooling

 
DSC Base Station

The new HP Dynamic Smart Cooling (DSC) technology helps you tackle one of the most critical issues in today's data centers - power and cooling. DSC will enable you to change data center energy costs from a fixed to a variable cost, significantly increase your IT scaling headroom, and ensure complete confidence that you're running a much more efficient data center - helping you drive towards a more adaptive infrastructure.

Why Dynamic Smart Cooling?

  • Increase cooling capacity up to 80% of rated CRAH/CRAC utilization from typical 30–50% utilization.
  • Energy savings: Reduces cooling costs by up to 45% (depending on cooling plant)
  • Resiliency: Ensures automatic re-tuning if changes or disturbances threaten air-conditioning reliability
  • Increased efficiency: Supports higher rack operating temperature due to quick response times; enables higher chilled water temperature for energy savings
  • Computer room air conditioners (CRAC) consolidation: Enables fewer CRACs for same level of reliability with usage flexibility for increased savings
  • Flexibility: Choose to apply increased savings to IT scalability or other critical data center needs

HP Dynamic Smart Cooling bridges the legacy gap between IT and facilities managers for significant cost savings to create a more adaptive infrastructure. Typically, IT equipment has simply existed within the data center, with power and cooling capacity increasingly limiting the ability to efficiently deploy new technologies. For the first time, Dynamic Smart Cooling - the latest HP innovation produced from over a decade of research efforts - enables the equipment to interact with the facilities that support the data center, driving maximum efficiency.

NOTE: For more information please see:


At a Glance

HP Dynamic Smart Cooling includes a DSC Energy Manager Control Node, DSC Base Stations and DSC Intake Sensors. Additionally, DSC Exhaust Sensors may be added to enhance DSC's capabilities by allowing the detection of no flow, reverse flow or low load conditions.

For additional information please visit: http://www.hp.com/go/dsc and http://www.hp.com/go/btc

Protected by HP Services and a three-year, on-site limited global warranty. Certain restrictions and exclusions apply.

contents
 Overview      Product Features      Service & Support      Models      Related Options      Technical Specifications line.gif (50 bytes)

Product Features

HP DSC Energy Manager Control Node

As the brains of the operation, the DSC Energy Manager Control Node is a HP ProLiant DL380 G5 running Microsoft Windows Server 2003, Microsoft SQL Server 2005 and HP DSC Energy Management software. The DSC Energy Manager Control Node communicates with the facility's Computer Room Air Conditioners to provide only the amount of cooling required at a point in time, and no more.


HP DSC Base Station

HP DSC Base Stations are assigned to individual racks and collect temperature data from DSC Intake and Exhaust Sensors associated with that rack. The DSC Base Station then reports that information every 15 seconds to the DSC Energy Manager Control Node.


HP DSC Intake & Exhaust Sensors

HP DSC Intake & Exhaust Sensors are arrays of thermal sensors. DSC Intake Sensors are installed in front of a rack, while the optional DSC Exhaust Sensors are installed at the rear of the rack. The intake sensors allow DSC to determine if the air going into a rack is cool enough for the rack's load. The optional exhaust sensors extend DSC capabilities by allowing DSC to detect no flow, reverse flow or low load conditions.

contents
 Overview      Product Features      Service & Support      Models      Related Options      Technical Specifications line.gif (50 bytes)

Service & Support

Deployment Service

The required deployment service for HP Dynamic Smart Cooling is ordered via part number HF801A1 and requires a price to be entered since this is a custom bid service. The price is available in the final quote that was provided to the customer and must be entered at the time the order was placed.


Assessment Service

The HP DSC Thermal Assessment is ordered, and invoiced, separately under part number HA536A1. This provides an analysis comparing industry/HP best practices to the customer's current data center environment and readiness for Dynamic Smart Cooling. In addition, HP will perform 3D modeling of the entire data center supply and return air flows and will provide a written report that includes observations, thermal model results, DSC readiness results, and recommendations for improvement.


Service and Support

This product is covered by a global limited warranty and supported by HP Services and a worldwide network of service providers. Hardware diagnostic support and repair is available for three years from date of purchase. Additional support may be covered under the warranty or available for an additional fee. Enhancements to warranty services are available through HP Care Pack services or customized service agreements.

NOTE: DSC Limited Warranty includes 3 year Parts, 3 year Labor, 3-year on-site support. This warranty supports the DSC Energy Manager Control Node, DSC Base Station and DSC Intake & Exhaust Sensors. HP DSC Energy Management Control Software includes 1 year next business day support.

HP services provide continuous care and support expertise with committed response designed to meet your IT and business needs.

HP Services, an industry leader in provision of multi vender support solutions provides a range of support services designed to meet the varying needs of business. Whether an SMB or large global corporation HP has a HP Dynamic Smart Cooling support offer to help you speedily deploy and maximize system uptime.

Available Support Upgrades:

  • Next Business Day On-site Service, 5-Day x 9-Hour Coverage, 3 Years.
  • 4-Hour On-site Service, 5-Day x 13-Hour Coverage, 1 or 3 Years.
  • 4-Hour On-site Service, 7-Day x 24-Hour Coverage, 1 or 3 Years.
contents
 Overview      Product Features      Service & Support      Models      Related Options      Technical Specifications line.gif (50 bytes)

Models

NOTE: Each HP DSC Base Station supports one Intake Sensor Array and typically one base station is placed at every second rack in a data center. Universal sensors are for non-HP racks.
HP DSC Configuration
NOTE: Determine quantity of HP DSC Base Station and Intake Sensor Arrays to purchase and choose the HP DSC Energy Manager Control Node that supports at least that quantity.
Required Options (one of the following from each category unless otherwise noted)
HP DSC Energy Manager Control Nodes HP DSC Energy Manager Control Node Unlimited (1000 base stations)
AJ350A
HP DSC Energy Manager Control Node Large (500 base stations)
AJ353A
HP DSC Energy Manager Control Node Medium (250 base stations)
AJ352A
HP DSC Energy Manager Control Node Small (125 base stations)
AJ351A
NOTE: Order only one DSC Energy Manager Control Node per managed area. A managed area is typically one room of a data center.
HP DSC Base Stations HP DSC Base Station. Single
AH979A
HP DSC Base Station. Bulk
AH980A
NOTE: Bulk packs contain 20 base stations.
HP DSC Intake Sensors HP DSC Intake Sensors (Unv.). Single
AH981A
HP DSC Intake Sensors (Universal). Bulk
AH982A
HP DSC Intake Sensors (10k). Single
AH983A
HP DSC Intake Sensors (10k). Bulk
AH984A
NOTE: HP DSC Intake Sensors (10k) are only for HP 10k G1 & G2 42U & 47U racks. All other racks use the DSC Intake Sensors (Universal).
NOTE: DSC Exhaust Sensors are also available to extend the capabilities of DSC
NOTE: Order the same quantity of sensors as base stations. Bulk packs contain 20 units.
HP DSC Exhaust Sensors HP DSC Exhaust Sensors, Single
AH985A
HP DSC Exhaust Sensors, Bulk
AH986A
NOTE: Exhaust sensors extend the capabilities of DSC by allowing it to detect no flow, reverse flow and low load conditions.  
contents
 Overview      Product Features      Service & Support      Models      Related Options      Technical Specifications line.gif (50 bytes)

Related Options

HP Rack 10000 G2 Series (Graphite Metallic) 10642 G2 (42U) Rack Cabinet – Pallet
AF001A
10642 G2 (42U) Rack Cabinet – Shock Pallet
AF002A
10642 G2 (42U) Rack Cabinet – Crated
AF003A
10642 G2 (42U) Rack Cabinet, with Extension – Shock Pallet
AF004A
10642 G2 (42U) Rack Shock Pallet- for field racking (NA only)
AF007A
10636 G2 (36U) Rack Cabinet – Shock Pallet
AF011A
10636 G2 (36U) Rack Cabinet – Crated
AF012A
10636 G2 (36U) Rack Cabinet, with Extension – Shock Pallet
AF013A
10636 G2 (36U) Rack Cabinet, without door – Shock Pallet
AF014A
10647 G2 (47U) Rack Cabinet – Pallet
AF031A
10842 G2 (42U) Rack Cabinet Shock
AF042A
10842 G2 (42U) Rack Cabinet Pallet
AF041A
NOTE: Please see the Rack 10000 G2 QuickSpecs for additional part numbers and Technical Specifications such as height, width, depth, weight, and color:
http://h18000.www1.hp.com/products/quickspecs/12402_div/12402_div.html (Worldwide)
NOTE: For additional information regarding Rack Cabinets, please see the following URL: http://www.hp.com/go/rackandpower.
 

Service and Support Offerings (HP Care Pack Services) NOTE: It is highly recommended that the HP DSC Base Stations and Energy Managers have the same support level.
For the HP DSC Energy Managers, HP support services are mandatory. Customers must choose from one of the HP Care Pack services below:
HP DSC Energy Manager Services  
HP 1y SW Support
HA106A1#4YU
HP 1y Support Plus SVC
HA109A1#4YU
HP 1y Support Plus 24 SVC
HA110A1#4YU
HP 3y SW Support
HA106A3#4YU
HP 3y Support Plus SVC
HA109A3#4YU
HP 3y Support Plus 24 SVC
HA110A3#4YU
contents
 Overview      Product Features      Service & Support      Models      Related Options      Technical Specifications line.gif (50 bytes)

Technical Specifications

DSC Sensor Arrays & Base Station

 
DSC Intake Sensor for HP 10k Series Racks
NOTE: DSC Intake Sensor Arrays for HP 10k Series Racks are mounted at the front of the rack. Each array consists of five thermal sensors.

DSC Intake Sensors (Universal)
NOTE: DSC Universal Intake Sensor Arrays work with many third party non-HP racks. Like the arrays for the HP 10k Series racks, they are installed at the front of the rack and consist of five thermal sensors per array.

DSC Exhaust Sensors
NOTE: DSC Exhaust Sensors mount at the rear of racks, and like the intake sensors, consist of five thermal sensors. Exhaust sensors are not required for DSC to function properly. They are an option that extends the capabilities of DSC to enable the DSC Energy Manager to detect no flow, reverse flow or low load conditions in racks equipped with the exhaust sensors.

DSC Base Station – Front Panel View

DSC Base Station – Rear Panel View
Each DSC Base Station supports up to two sensor arrays: one intake sensor and one exhaust sensor. Only one base station is assigned per monitored rack. Typically, every second rack in a data center would be monitored and have a base station assigned to it.

HP DSC Base Station Shipping Dimensions Height 4.0in (102 mm)
Width 8.13 (207 mm)
Depth 10.63in (270 mm)
Weight Unboxed 2.2 lb (1.0 Kg)
Shipping 2.85 lb (1.3 Kg)
Temperature Range Operating 50° to 158° F (10° to 70° C)
Non-Operating -4° to 158° F (-20° to 70° C)
Relative Humidity
(non-condensing)
Operating 10% to 90%
Non-Operating 5% to 95%
Wet Bulb Temperature Non-Operating 101.7° F (38.7° C)

Power Input Characteristics Input voltage 90 - 264Vrms
Input frequency 47 - 63Hz
Input current 1.5A at 100VAC
Inrush Current 100A at 240VAC
Leakage Current Less than 3.5mA at 250VAC/60Hz
Power Supply Input Power Connection C5
Type On-board AC/DC

Environment-friendly Products and Approach End-of-life Management and Recycling

Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling programs in many geographic areas. For trade-in information, please go to http://www.hp.com/go/green. To recycle your product, please go to: http://www.hp.com/go/green or contact your nearest HP sales office. Products returned to HP will be recycled, recovered or disposed of in a responsible manner.

The EU WEEE directive (2002/95/EC) requires manufacturers to provide treatment information for each product type for use by treatment facilities. This information (product disassembly instructions) is posted on the Hewlett Packard web site at: http://www.hp.com/go/green. These instructions may be used by recyclers and other WEEE treatment facilities as well as HP OEM customers who integrate and re-sell HP equipment.


© Copyright 2007 Hewlett-Packard Development Company, L.P.

The information contained herein is subject to change without notice.

Microsoft and Windows NT are US registered trademarks of Microsoft Corporation. Intel is a US registered trademark of Intel Corporation.

The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial errors or omissions contained herein.


   DA-12868 1 - Version 1 - October 19, 2007