Freestanding and self contained, the HP Power Distribution Rack speeds deployment and increases branch circuits to the data center. The HP PDR and pre-configured whips allow for easy addition of circuits without long cable runs. |
 |
 |
|
 |
|
 |
|
 |
 |
|
 |
Dual power paths from input to output, including dual management displays provide no single point of failure. |
 |
 |
|
 |
 |
 |
High amperage inputs allow redundant support of over twenty 5KW racks of equipment or over a dozen 8KW rack. A 60 amp maximum branch circuit size means that even extreme densities can be supported. |
 |
 |
|
 |
 |
 |
Transformers, even in smaller capacity systems, can easily generate 10,000 BTUs. The transformer-less design of the HP PDR allows you move transformers off of the data center floor and the pre-configured whips reduce the amount of cable under a raise floor preventing air dams. |
 |
|